Page 1 of 3
© 2018 IronRidge, Inc. Knockout Tile Certification Letter - 1
28357 Industrial Blvd
Hayward, CA 94545
1-800-227-9523
IronRidge.com
Attn: Corey Geiger, COO, IronRidge Inc.
Date: December 10th, 2018
Re: Structural Certification for IronRidge Knockout Tile Roof Attachment
This letter addresses the structural capacity of the IronRidge Knockout Tile for use as a tile roof attachment for
flush mounted PV solar systems. Knockout Tile assembly consists of an extruded aluminum base, a rail
mounting bracket (L-foot), and an aluminum tile replacement flashing fastened to the assembly. The base is
attached to an underlying roof rafter using one (1) 5/16” stainless steel lag bolt and the L-foot is secured to the
base by a 5/16" stainless steel threaded stud and nut. Assembly of Knockout Tile and accompanying hardware
shall be installed in accordance with IronRidge Knockout Tile Installation Manual. Full assembly details are
shown in Exhibit EX-0018.
The referenced uplift, compression and lateral capacities of Knockout Tile tabulated below are based on
mechanical load tests conducted along the four load directions shown in Figure 1, using a Universal Instron
Test Unit, conforming to the following standards:
ASTM D1761-12, Standard Test Methods for Mechanical Fasteners in Wood
ASTM B 557-15, Standard Test Method for Tension Testing Wrought and Cast Aluminum and
Magnesium-Alloy Products
NDS-2015, National Design Specification (NDS) for Wood Construction
ICC-428, Acceptance Criteria for Modular Framing Systems Used to Support Photovoltaic (PV)
Modules
For each load test, a Knockout Tile assembly was installed onto a preconditioned sample roof deck composed
of 15/32” OSB board and 2x4 Douglas Fir rafters. The measured moisture contents of the conditioned roof
decks ranged from 10% to 12%, and average specific gravity applying to uplift and lateral (across slope)
directions is 0.47. For each test, loads were applied at the highest slot position on the L-foot as shown in
Figure 1 and testing was performed to consider all orientations of L-foot and base as allowed per the Knockout
Tile Installation Manual. Table 1 below summarizes the average peak load, its associated failure mode, and
the calculated allowable capacity for the respective load direction. The listed average peak load reflects the
orientation of L-foot and base which results in the lowest capacity and can be applied to other allowable
orientations.
For wood species with specific gravity other than 0.47, capacities associated with lag pull out failure mode
(uplift & lateral across slope) shall be adjusted per American Wood Counsel (AWC) National Design
Specification Eq. (12.2-1). Adjusted results for various wood species are presented in Table 2 below.
Page 2 of 3
© 2018 IronRidge, Inc. Knockout Tile Certification Letter - 2
28357 Industrial Blvd
Hayward, CA 94545
1-800-227-9523
IronRidge.com
Table 1 Notes:
(1) Capacity applies to rafter size of 2x4 or greater at 24” O.C. or less, deck thickness 15/32” or greater, and are based on securing lag bolts within the
center 1/3 of rafter width with a minimum 2.5” end distance.
(2) For rafter specific gravity not equal to 0.47, uplift and lateral (across slope) capacities shall be adjusted and can be referenced in Table 2.
(3) Deviation reflects the variance of the highest or the lowest test value from the group mean for the respective load direction.
(4) Safety Factor is associated with the respective failure mode determined by the specific code referenced on Page 1.
(5) Allowable capacity is equal to Average Peak Load divided by its associated Safety Factor.
Table 2 Notes:
(1) Wood specific gravity is per NDS-2015 Table 12.3.3.A.
(2) Allowable Capacity = Table 1 Allowable Capacity x Adjustment Factor
Adjustment Factor = (Wood Density/0.47)3/2 per (AWC) National Design Specification Eq. (12.2-1)
Sincerely,
Gang Xuan, SE
Senior Structural Engineer
Load Direction Specimen Quantity Average Peak Load at
Failure (lbs)
Deviation of Test
Results (3) Critical Failure Mode Safety Factor (4) Allowable Capacity
(lbs) (5)
Uplift Load
Perpendicular to Roof
Surface(2)
4 1440 4% Lag Bolt Pull-out 3.0 480
Compression Load
Perpendicular to Roof
Surface
4 2385 7% OSB Deck Rupture 2.54 939
Lateral Load Parallel to
Rafter (Downslope) 4 461 2% Rupture of Base at
Lag Bolt Connection 1.95 237
Lateral Load
Perpendicular to Rafter
(Across Slope)(2)
4 592 9% Lag Bolt Pull-out 3.00 197
Table 1: IronRidge Knockout Tile Roof Assembly Allowable Capacities (1)
Wood Species NDS Assigned Specific Gravity(1) Allowable Uplift Capacity (lbs)(2) Allowable Lateral (Across Slope)
Capacity (lbs)(2)
Southern Pine 0.55 608 249
Douglas Fir-Larch 0.5 527 216
Douglas Fir-South 0.46 465 191
Hem-Fir (North) 0.46 465 191
Hem-Fir 0.43 420 172
Spruce-Pine-Fir 0.42 405 166
Table 2: Allowable Capacities Adjusted for Various Wood Species
Page 3 of 3
2.0
6.13
3.55
5.02
1
2 3
4
5
6
7
8
EXHIBIT: EX-0018
ITEM NO. DESCRIPTION
1 NUT, FLANGE, HEX, 5/16-18 SS
2 WASHER, EPDM BACKED
3 L-FOOT
4 BOLT, LAG 5/16 X 4"
5 ASSY, BASE
6 FLASHING, TILE REPLACEMENT, S-TILE
7 FLASHING, TILE REPLACEMENT, FLAT TILE
8 FLASHING, TILE REPLACEMENT, W-TILE Assy, Knockout Tile
DWG. NO. EX-0018